Укр|Eng|Рус
Ukraine
Catalog   /   Home & Renovation   /   Electrical Equipment   /   UPS

Comparison FrimeCom GP-2000 2000 VA vs Full Energy BBGP-220/20Pro 2000 VA
9 Ah

Add to comparison
FrimeCom GP-2000 2000 VA
Full Energy BBGP-220/20Pro 2000 VA 9 Ah
FrimeCom GP-2000 2000 VAFull Energy BBGP-220/20Pro 2000 VA
9 Ah
Compare prices 2Compare prices 1
TOP sellers
Typebackback
Form factorstandard (Tower)standard (Tower)
Switching to battery8 ms6 ms
Input
Input voltage1 phase (230V)1 phase (230V)
Input voltage range140 – 290 V150 – 260 V
Max. current1 A
Input frequency50 Hz
Bypass (direct connection)is absentis absent
Output
Output voltage1 phase (230V)1 phase (230V)
Max. output power2000 VA2000 VA
Rated output power1200 W1200 W
Output waveformsimilar to a sinusoid (approximated)similar to a sinusoid (approximated)
Output frequency50 Hz50 Hz
Redundant sockets44
Socket typetype F (Schuko)type F (Schuko)
Battery
Supplied battery(s) capacity9 Ah9 Ah
Voltage of the 1 battery in set12 V12 V
Batteries22
Full charge time360 min
Cold start
Protection
Protection
short circuit protection
overload protection
sound alarm
short circuit protection
overload protection
sound alarm
Fuseauto
General
Screen
Operating temperature0 – 40 °C
Noise level40 dB
Dimensions (HxWxD)185x130x333 mm195x122x360 mm
Weight13.1 kg
Added to E-Catalogjuly 2023may 2023

Switching to battery

The time required to transfer the load from mains power to battery power. In standby and interactive UPSs (see Type), a short-term power failure occurs at this moment — accordingly, the shorter the time to switch to the battery, the more uniform the power supply is provided by the source during a power failure. Ideally, the switching time for the traditional 50 Hz AC frequency should be less than 5 ms (a quarter of one cycle of the sine wave). With inverter UPSs, the transfer time is, by definition, zero.

Input voltage range

In this case, the input voltage range is implied, in which the UPS is able to supply a stable voltage to the load only due to its own regulators, without switching to the battery. For redundant UPSs (see "Type") this range is quite small, approximately 190 to 260 V; for interactive and especially inverter ones, it is much wider. Some UPS models allow you to manually set the input voltage range.

Max. current

The maximum current drawn by the UPS. In fact, the current reaches its maximum value only when the UPS is operating from the mains with maximum load power and a completely discharged battery. However, when calculating the load on the power grid, this parameter should be taken into account.

Input frequency

The operating frequency of the alternating current supplied to the input of the UPS — or more precisely, the frequency range of this current in which the device can supply the required power to the load due to its own regulators, without using a battery. When this range is exceeded, the UPS switches to battery mode. The smallest input voltage range is reserved for standby UPSs (see "Type"), the largest for inverter UPSs.

Full charge time

The time it takes to fully charge the UPS battery. Note that in this case, this time is calculated according to special rules: not from 0 to 100% of the charge, but from a state in which it is impossible to maintain half the load, up to 90% of the charge. Of course, a full charge will take a little longer. However, this data is closer to practice than the “from 0 to 100%” calculation: the inability to work at half load makes the UPS practically useless, and this condition can be taken as zero, and 90% of the battery is already able to provide a good guarantee in case of a power failure.

Cold start

The ability to turn on the uninterruptible power supply in the "cold start" mode.

A cold start is a turn-on mode in which there is no external power, and the load connected to the UPS is powered immediately from the uninterruptible battery (which, of course, must be charged). This mode is especially useful in emergency cases — for example, if you urgently need to print a document, but there is no light.

Fuse

Fuses are used to protect the UPS from a critical increase in current strength: at the right time, they open the circuit, preventing unpleasant consequences. Today, these types of fuses are used.

— Melting. At a critical current strength, the conductive element in such a fuse melts and opens the circuit. The fusible protection is disposable, after operation such a fuse must be replaced.

— Automatic. Such a fuse has a sensor that monitors the current strength and opens the contacts at the right time. Its main difference from fusible is reusability: after operation, the circuit can be closed again with literally one press of the button on the fuse.

Screen

The presence of the UPS own display makes management more convenient. Various operating characteristics can be displayed on the external screen: mains voltage and frequency, operating mode, load level, battery charge, bypass status, etc.

Operating temperature

Ambient temperature range in which the UPS is guaranteed to maintain normal operation.

All modern "uninterruptible" without problems endure the temperatures typical for residential and office premises. Therefore, it makes sense to pay attention to this parameter if the device is planned to be used in more extreme conditions — for example, in an unheated room, or vice versa, in a production workshop with a high air temperature. At the same time, it's ok to take a margin for temperature: this will give a guarantee in case of unforeseen situations, besides, the wider the temperature range, the higher the overall resistance to adverse conditions.
Price graph
FrimeCom GP-2000 often compared